Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED ALL PAPER WORK |
|
| 12/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WAITING ON PAPER WORK |
|
| 12/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MULTI-WIRE CIRCUITS TO POWER POLES TO BE AS PER 605.7 2. MC CABLE TO TERMINATE 3. GROUND JUNCTION BOX 4. NEED LETTER FOR DUAL SWITCHING OF LIGHTS 5. NEED PLANS FOR A/C CONTROLS 6. EQUIPMENT IN CONTROL BOX TO BE LISTED & LABELED 7. TIGHTEN LOOSE FITTINGS OFFICE FURNITURE 8. GFI NOT WORKING 9. EM LIGHTING NOT WORKING ALSO EXIT TO BE AS PER 700.12 10. PANEL DIRECTORIES TO BE AS PER 408.4 11. NEED DISCONNECTING MEANS FOR SERVER ROOM AC 440 |