Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/04/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 11/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH PREVIOUS INSPECTIONS 1 & 4 RECEIVED LETTER FOR LIGHT FIXTURES |
|
| 11/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEM 1, 4 & 5 |
|
| 11/16/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT VDV CABLING PER 725.3 & 6, 800.3 & 6, 300.11 2. FILL UNUSED CONDUIT OPENINGS 3. IF M/C WHIPS ARE SUPPORTED THEY MUST BE AS PER 300.11 4. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING 5. FIXTURES IN ROOM 239 NOT AS PLAN - ALSO, ATTACH TO GRID 410.16 |