Permit: T07CM03277

Parcel: 12606204A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
12/12/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/04/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
11/30/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS INSPECTIONS 1 & 4

RECEIVED LETTER FOR LIGHT FIXTURES
11/19/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FINISH PREVIOUS ITEM 1, 4 & 5
11/16/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1. SUPPORT VDV CABLING PER 725.3 & 6, 800.3 & 6, 300.11
2. FILL UNUSED CONDUIT OPENINGS
3. IF M/C WHIPS ARE SUPPORTED THEY MUST BE
AS PER 300.11
4. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING
5. FIXTURES IN ROOM 239 NOT AS PLAN -
ALSO, ATTACH TO GRID 410.16