Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 08/14/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/04/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* F, E, M, P 1. FINISH HANDICAP PARKING SIGNAGE AND HAND RAIL 2. CHECK ON HANDICAP PARKING SITE PLAN |
|
| 04/25/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* REMOVE SHELVING FROM HALLWAY OK FOR TEMP C OF O PREVIOUS NOT 3 - NOT FULFILLED |
|
| 04/21/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HARD, NON-POROUS, IMPERMEABLE SURFACE REQUIRED ON WALLS WITHIN 2' OF WATER CLOSET (CHAPTER 12 IBC) YOUR F.R.P SHOULD BE ON NORTH WALL 2. MAX. 5LB. FORCE ALLOWED FOR OPENING DOORS (RESTROOM) 3. INDICATE ACCESSIBLE ROUTE ON SITE PLAN INDICATE ACCESSIBLE PARKING ON SITE PLAN WHERE IS ACCESSIBLE ROUTE FROM PUBLIC WAY INDICATE ON PLANS COMPLIANCE WITH SECTION 3409 OF IBC |