Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/04/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGE OK IF LAMINATE FLOORING IF TILE, CLOSET FLANGE SHALL REST ON FINISHED FLOOR |
|
| 11/15/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* YARD WATER INSTALLED PER RED LINES OK TO BACKFILL IN ACCORDANCE W/UPC SEC 315.4 HAND SHADE PIPE BEFORE USING MECHANICAL EQUIPT. TO COMPLETE BACKFILL |
|
| 11/14/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* (YARD WATER INSPECTION) PROVIDE AN ACCURATE SITE PLAN AND INSTALL PER PLAN NO ADHESIVE TAPE ON PEX PVC SPECIFIED PROVIDE A TUCSON WATER PERMIT FOR NEW RP REMOVE ROCKS FROM TRENCH |
|
| 11/01/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DOMESTIC COPPER OK COMPLETE INSTALLATION OF HW PIPE INSULATION SUPPORT W.B OK TO COVER WALLS SUPPORT ABV CEILING WATER PIPING OVER TOILET RM SEPARATE FROM TOUCHING METAL AIR PIPING NOT PER PLAN WILL INSPECT CLOSET FLANGE AFTER F.F |
|
| 10/05/2007 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 09/14/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER FLOOR DWV TEST TO VENTS ABV CEILING OK |