Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & SOFFITS |
|
| 11/01/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT MC CABLE AT TOP PLATES 2. SEAL UNUSED CONDUIT OPENING 3. EXISTING OPENINGS TO BE PER 517.13 - FLEX IS NOT A GROUND PATH PER 250 4. VDV TO BE SUPPORTED AS PER 725.6, 800.6, 300.11 5. BOX OVERFILLED 6. NEED TO SEE POWER FOR CHAIR LIGHTS 7. FIXTURES TO BE ATTACHED TO GRID 410.16 IF SCREWS 4 ON CORNERS OR 2 ON CENTER |
|
| 09/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK U.G PER NOTES LAST INSP. |
|
| 09/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NOTE: EAST CHAIR CONDUIT ALMOST AT 360 DEG. OK 3 POWER FLOOR BOXES 1. CONDUIT FOR VDV CABLING TO BE AS PER ARTICLE 300 2. CONDUIT FOR FUTURE NOT INSTALLED |