Permit: T07CM02796

Parcel: 11005021A


Addresses:

2959 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/06/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
WORK NOT REFLECTIVE OF PLANS

OK CEILING SUBJECT TO PLAN REVISIONS
08/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. M/C CABLE TO TERMINATE PER MANUFACTURES LISTING
2. NEED TO SEE CONDUITS IN COLUMNS
3. SUPPORT M/C CABLES WITHIN 12" OF CANS & BOXES 330.30
4. USE APPROVED STRAPS OR SUPPORT METHODS FOR M/C CABLES
5. TIGHTEN LOOSE CONDUIT FITTINGS
6. JUNCTION BOXES TO BE ACCESSIBLE
7. SUPPORT VDV CABLES 815.6 & 820.6
8. CEILING OUTLET NOT ON PLANS
08/21/2007 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled