Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02796
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WORK NOT REFLECTIVE OF PLANS OK CEILING SUBJECT TO PLAN REVISIONS |
|
| 08/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. M/C CABLE TO TERMINATE PER MANUFACTURES LISTING 2. NEED TO SEE CONDUITS IN COLUMNS 3. SUPPORT M/C CABLES WITHIN 12" OF CANS & BOXES 330.30 4. USE APPROVED STRAPS OR SUPPORT METHODS FOR M/C CABLES 5. TIGHTEN LOOSE CONDUIT FITTINGS 6. JUNCTION BOXES TO BE ACCESSIBLE 7. SUPPORT VDV CABLES 815.6 & 820.6 8. CEILING OUTLET NOT ON PLANS |
|
| 08/21/2007 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled |