Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2008 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 09/05/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode connection Provide proof of an approved ufer ground or install tw0 8 ft ground rods 6 ft apart connected to the service panel with a continous #4 conductor Splicing ground wire with split bolts not allowed Put address on panel |