Permit: T07CM02727

Parcel: 123050160


Addresses:

2035 E EDISON ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/25/2008 ELECTRIC - SERVICE UPGRADE Approved
09/05/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode connection
Provide proof of an approved ufer ground or install tw0 8 ft ground rods 6 ft apart connected to the service panel with a continous #4 conductor
Splicing ground wire with split bolts not allowed
Put address on panel