Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. CIRCUIT DIRECTORY TO BE PERMANENT AND LABELED AS 408.4 3. CLEAN EXCESS DIRT & TRASH FROM BOTTOM OF PANEL 4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR IN RACEWAY 5. TIGHTEN LOOSE WATER HEATER FITTINGS 6. GROUND TERMINATION TO BE 3/4 OF A TURN UNDER SCREW 7. BOND DISCONNECT ENCLOSURE 8. LABEL DISCONNECT 9. INSTALL FUSES FOR DISCONNECT 10. SUPPORT CONDUIT AS PER CODE |