Permit: T07CM02470

Parcel: 121060070


Addresses:

5633 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02470

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2. CIRCUIT DIRECTORY TO BE PERMANENT AND
LABELED AS 408.4
3. CLEAN EXCESS DIRT & TRASH FROM BOTTOM OF PANEL
4. CORRECTLY IDENTIFY GROUNDED CONDUCTOR IN RACEWAY
5. TIGHTEN LOOSE WATER HEATER FITTINGS
6. GROUND TERMINATION TO BE 3/4 OF A TURN UNDER SCREW
7. BOND DISCONNECT ENCLOSURE
8. LABEL DISCONNECT
9. INSTALL FUSES FOR DISCONNECT
10. SUPPORT CONDUIT AS PER CODE