Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T07CM02468
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
06/20/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK POLE BASE AGAIN IN BACK |
|
04/21/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* PROVIDE LETTER FROM ENG. OF RECORD TO DELETE GUTTERS USED AT SERVICES |
|
02/29/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SECONDARYS FROM TEP X-FORMER TO SES |
|
01/24/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PANEL FEEDER BELOW SLAB |
|
01/09/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3/4" CONDUITS RUN THRU BLD. FOR WEST MONUMENT SIGNS |
|
11/19/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK WALL 2"A" THRU 2"D" WALL WITH STUB UPS OK 2) OK UFERS 2"A" THRU 2"D" |
|
11/13/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK DATA/FEEDERS BELOW SLAB AND STUB UPS AT NORTH EXTERIOR WALL AREA |
|
11/05/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SERVICE SECONDARYS 4" |