Permit: T07CM02315

Parcel: 14122004G


Addresses:

8500 S RITA RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/20/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
09/21/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
CONTINUATION OF 4" BUILDING DRAIN UP TO 10' AFF
COLUMN LINE D-5
09/10/2007 PLUMBING - ROUGH, SOIL Partial Approval
08/23/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PRE-SLAB AIR COMPRESSOR PAD & TOWER PAD OK
WATER TEST 2" FS UNDERGROUND THRU ROOF LOADING DOCK AREA OK
WATER TEST 4" FS UNDERGROUND ONLY ROOM D.I 28 OK
6" SDR 35 WITH DUCTILE IRON CROSSING FROM EXISTING 8" BACK TO EXISTING BUILDING AT EAST END AIR TEST OK

1. SHALL SEE CONNECTION OF 4" LATERALS TO AREA DRAINAGES
08/17/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FROM TOWER AREA
WATER TEST UNDERGROUND FROM 4" END OF LINE CLEANOUT MY INITIAL M2.12 SOUTH INCLUDING (4) FLOOR SINKS FOR LTPCWP AND MTPCWP BACK TO 2' FROM MAIN SEWER
08/10/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 2" FROM EXISTING FOR SINK AT ROOM 131 WATER TEST UNDERGROUND OK
2) PRE-SLAB PIPE WRAPS AND TRAP PRIMERS AND FLOOR DRAINS OK ROOM 121 AND 123
3) 6" SDR 35 FROM EXISTING 3" APP 15' FROM CLEANOUT #2 GOING EAST. BEDDING LAYING, TRACER, SHADING OK
4) WILL CHECK AIR TEST AT LATER DATE
08/02/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST RESTROOM 121, 123 UNDERGROUND PER REDLINE INCLUDING P-5H OK
PRE-SLAB CHILLER SLAB OK
07/27/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FROM INITIAL PAGE M2.12
4" UPSTREAM SANITARY DRAINAGE FOR (6)
FLOOR SINKS FOR CHILLER PADS PER PLAN WATER TEST OK
07/25/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PRE-SLAB PIPE WRAPS & TRAP PRIMERS, FLOOR CLEANOUTS RESTROOM 109, 110, EWC & SINK SOUTH END OK

4" SANITARY DRAIN PER REDLINE PAGE M3.02 FROM EXISTING TO MY INITIAL WATER TEST OK

4" SANITARY DRAIN FROM END OF LINE C.O FLOOR SINK TO 2' SOUTH OF BOILER PAD WATER TEST OK

4" SANITARY DRAIN FROM END OF LINE C.O THRU (4) FLOOR SINKS TO 2' NORTH OF COMPRESSOR PAD WATER TEST OK PER REDLINE.
07/20/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND FOR PAGE M3.02 OK
DEMO OLD SANITARY PARTIAL OK
1. SHALL PROVIDE STAMPED LETTER FROM ENGINEER GIVING OK FOR NO-HUB IN PLACE OF HUB & SPIGOT UNDERGROUND SANITARY SEWER PIPING