Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CHECK WITH BUILDING INSPECTOR FOR CONTINUATION OF TEMP C OF O --- I HAVE NO ISSUES |
|
| 05/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. REMOVE OLD & PARTIAL DEMO OF WIRING @ BULK STORAGE 2. PROPERLY WIRE EM LIGHTING 3. NEED PROPER SIZE OVERCURRENT PROTECTION FOR CONDENSING UNITS @ BULK STORAGE 4. HAVE ENGINEER VERIFY IF BULK STORAGE PLANT IS HAZARDOUS LOCATION 5. LABEL ALL SWITCHES ON DISTRIBUTION SWITCH BOARDS |
|
| 05/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK LISTING OF DISCONNECTS FOR FAN UNITS IN PENTHOUSES |
|
| 05/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL PROPER SIZE FUSES FOR ET-2 2. LABEL DISCONNECTS ON EM DISTRIBUTION PANEL 3. NEED SMALL SET OF REVISED DRAWINGS FOR INSPECTIONS. |
|
| 05/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK DISCONNECTS PHASE II FIRST FLOOR |
|
| 05/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK PANELS PP2D, RP2E, RP2HA, RP2J, RP2A, PP2A, LP3A 2. OK CEILINGS TOOL CHASE #134, 135 3. OK XFMR ET-13 4. OK MCCM2F 5. KEEP AREAS IN FRONT OF PANEL, XFMRS, SWBD'S, ETC. CLEAR 6. NEED FULL SET OF PLANS WITH APPROVED REVISIONS |
|
| 05/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. MEETING TO DISCUSS PREVIOUS INSPECTION ITEMS 2. INSTALL PROTECTIVE BUSHING ON CONDUCTOR #4 OR LARGER VFD's 3. PROPERLY GROUND VFD's |
|
| 04/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ROOF CORRECTIONS MADE 2. PROPERLY GROUND DISCONNECTS PENTHOUSES 3. CLOSE OPEN KNOCKOUTS BOTH PENTHOUSES 4. INSTALL BOX COVERS BOTH PENTHOUSES 5. INSTALL LB COVERS BOTH PENTHOUSES 6. PROPERLY TAP CONTROL CIRCUIT FOR RIB RELAYS USE FORKED TERMINAL ENDS. TAP CONDUCTORS NOT PROTECTED FOR OVERCURRENT PROTECTION. IS THERE PLANS FOR ENERGY MANAGEMENT SYSTEM? 7. MARK DISCONNECTS SHOWING ALL CIRCUITS PENTHOUSE 8. DO NOT SEE LISTING MARK ON DISCONNECTS PENTHOUSE 9. NEED TO OPEN VFD's FOR INSPECTION |
|
| 04/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF INSPECTION 1. PROPERLY GROUND DISCONNECTS. NO TECH SCREWS. ONE WIRE PER TERMINAL ETC. 2. GFI RECEPTACLES WITH NO POWER 3. AC-1 NEEDS INDICATION ON NAME PLATE IF ELECTRIC HEAT INSTALLED. NEEDS PROPER OVERCURRENT PROTECTION 4. ROTTED SEAL TIGHT SHOULD BE REPLACED. |
|
| 04/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CHECK WITH BUILDING INSPECTOR FOR CONTINUATION OF TEMP C OF O -- I HAVE NO ISSUES |
|
| 03/25/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK EM LIGHTS 2ND FLOOR & HIGH BAYS EXIT LIGHT 2ND FLOOR NORTH EXIT TO BE TIED INTO NORMAL CIRCUIT FOR HALLWAY |
|
| 03/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PARTIAL FINAL 2ND FLOOR AS INDICATED ON PLANS |
|
| 03/21/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. HAVE REVERSE POLARITY RP3A-23 2. FLOOR RECEPTACLE NORTH CONFERENCE RM HAS NO POWER 3. SOME OFFICE FURNITURE HAS NO POWER 4. CHECK RECEPTACLES EXTEND PAST METAL FACE PLATES 5. INSPECTION OF 2ND FLOOR NORTH TO OVAL CONFERENCE ROOM |
|
| 03/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROPERLY STRAP MANUFACTURED CABLE ASSEMBLIES RM 222C 2. OK FINALS RMS 222, 222D, 222A, 227, 226 3. RECEPTACLES RM 222B HAVE NO POWER |
|
| 03/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PARTIAL FINAL FIRST FLOOR CHECK WITH BUILDING INSPECTOR FOR TCO FIRST FLOOR |
|
| 03/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* CHECK WITH BUILDING INSPECTOR FOR CONTINUATION OF TEMP C.O FOR 1ST FLOOR NORTHWEST PRODUCTION AREA. |
|
| 03/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK DISCONNECTS FOR UV PRINTER 2. OK PANELS PP2D, LP2A, RP2C |
|
| 02/28/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FINAL ON ROOMS 114, 114A, 113, 112, 111, 108, 109, 110 |
|
| 02/27/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RMS 114, 114A, 113, 112, 111, 108, 109, 110 1. 30 AMP CIRCUIT #10 BOND JUMPER TO BOX 2. CIRCUIT #2 TRIPPING 3. RECEPTACLE WITH REVERSE POLARITY 4. INSTALL MISSING PLATES 5. ALL BATHROOM RECEPTACLES TO BE GFI PROTECTED |
|
| 01/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK WALLS BREAK RM 107 2. OK CEILINGS RMS 222, 222B, 222C, 222D, 222A, 201G, 227 |
|
| 01/04/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/03/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. DISCONNECTS TO INDICATE EQUIPMENT SERVED 2. INSTALL STRAIN RELIEF ON CORD DROPPED RECEPTACLES 3. OK PARTIAL FINAL ON SLITTER ROOM |
|
| 12/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 12/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS 2. OK FINAL FOR POWER IN MACHINE SHOP RM 124 3. DOWN DRAFT HOODS MISSING CONNECTORS, NOT GROUNDED PROPERLY, RECEPTACLES NOT SUPPORTED PROPERLY, MISSING STRAPS ON EMT - GSE HOODS 4. OK FINAL FOR POWER RM 127A, 127 & OTHER AREAS AS INDICATED ON PLANS 5. OK WALLS AS INDICATED ON PLANS. |
|
| 11/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |