Permit: T07CM02315

Parcel: 14122004G


Addresses:

8500 S RITA RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/20/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CHECK WITH BUILDING INSPECTOR FOR CONTINUATION OF TEMP C OF O --- I HAVE NO ISSUES
05/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. REMOVE OLD & PARTIAL DEMO OF WIRING @ BULK STORAGE
2. PROPERLY WIRE EM LIGHTING
3. NEED PROPER SIZE OVERCURRENT PROTECTION FOR CONDENSING UNITS @ BULK STORAGE
4. HAVE ENGINEER VERIFY IF BULK STORAGE PLANT IS HAZARDOUS LOCATION
5. LABEL ALL SWITCHES ON DISTRIBUTION SWITCH BOARDS
05/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK LISTING OF DISCONNECTS FOR FAN UNITS IN PENTHOUSES
05/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL PROPER SIZE FUSES FOR ET-2
2. LABEL DISCONNECTS ON EM DISTRIBUTION PANEL
3. NEED SMALL SET OF REVISED DRAWINGS FOR INSPECTIONS.
05/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK DISCONNECTS PHASE II FIRST FLOOR
05/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK PANELS PP2D, RP2E, RP2HA, RP2J, RP2A, PP2A, LP3A
2. OK CEILINGS TOOL CHASE #134, 135
3. OK XFMR ET-13
4. OK MCCM2F
5. KEEP AREAS IN FRONT OF PANEL, XFMRS, SWBD'S, ETC. CLEAR
6. NEED FULL SET OF PLANS WITH APPROVED REVISIONS
05/06/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MEETING TO DISCUSS PREVIOUS INSPECTION ITEMS
2. INSTALL PROTECTIVE BUSHING ON CONDUCTOR #4 OR LARGER VFD's
3. PROPERLY GROUND VFD's
04/30/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ROOF CORRECTIONS MADE
2. PROPERLY GROUND DISCONNECTS PENTHOUSES
3. CLOSE OPEN KNOCKOUTS BOTH PENTHOUSES
4. INSTALL BOX COVERS BOTH PENTHOUSES
5. INSTALL LB COVERS BOTH PENTHOUSES
6. PROPERLY TAP CONTROL CIRCUIT FOR RIB RELAYS USE FORKED TERMINAL ENDS. TAP CONDUCTORS NOT PROTECTED FOR OVERCURRENT PROTECTION. IS THERE PLANS FOR ENERGY MANAGEMENT SYSTEM?
7. MARK DISCONNECTS SHOWING ALL CIRCUITS PENTHOUSE
8. DO NOT SEE LISTING MARK ON DISCONNECTS PENTHOUSE
9. NEED TO OPEN VFD's FOR INSPECTION
04/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF INSPECTION
1. PROPERLY GROUND DISCONNECTS. NO TECH SCREWS. ONE WIRE PER TERMINAL ETC.
2. GFI RECEPTACLES WITH NO POWER
3. AC-1 NEEDS INDICATION ON NAME PLATE IF ELECTRIC HEAT INSTALLED. NEEDS PROPER OVERCURRENT PROTECTION
4. ROTTED SEAL TIGHT SHOULD BE REPLACED.
04/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CHECK WITH BUILDING INSPECTOR FOR CONTINUATION OF TEMP C OF O -- I HAVE NO ISSUES
03/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK EM LIGHTS 2ND FLOOR & HIGH BAYS
EXIT LIGHT 2ND FLOOR NORTH EXIT TO BE TIED INTO NORMAL CIRCUIT FOR HALLWAY
03/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL FINAL 2ND FLOOR AS INDICATED ON PLANS
03/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. HAVE REVERSE POLARITY RP3A-23
2. FLOOR RECEPTACLE NORTH CONFERENCE RM
HAS NO POWER
3. SOME OFFICE FURNITURE HAS NO POWER
4. CHECK RECEPTACLES EXTEND PAST METAL FACE PLATES
5. INSPECTION OF 2ND FLOOR NORTH TO OVAL
CONFERENCE ROOM
03/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROPERLY STRAP MANUFACTURED CABLE ASSEMBLIES
RM 222C
2. OK FINALS RMS 222, 222D, 222A, 227, 226
3. RECEPTACLES RM 222B HAVE NO POWER
03/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL FINAL FIRST FLOOR
CHECK WITH BUILDING INSPECTOR FOR TCO FIRST FLOOR
03/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CHECK WITH BUILDING INSPECTOR FOR CONTINUATION OF TEMP C.O FOR 1ST FLOOR NORTHWEST PRODUCTION AREA.
03/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK DISCONNECTS FOR UV PRINTER
2. OK PANELS PP2D, LP2A, RP2C
02/28/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FINAL ON ROOMS 114, 114A, 113, 112, 111, 108, 109, 110
02/27/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RMS 114, 114A, 113, 112, 111, 108, 109, 110

1. 30 AMP CIRCUIT #10 BOND JUMPER TO BOX
2. CIRCUIT #2 TRIPPING
3. RECEPTACLE WITH REVERSE POLARITY
4. INSTALL MISSING PLATES
5. ALL BATHROOM RECEPTACLES TO BE GFI PROTECTED
01/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK WALLS BREAK RM 107
2. OK CEILINGS RMS 222, 222B, 222C, 222D, 222A, 201G, 227
01/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. DISCONNECTS TO INDICATE EQUIPMENT SERVED
2. INSTALL STRAIN RELIEF ON CORD DROPPED RECEPTACLES
3. OK PARTIAL FINAL ON SLITTER ROOM
12/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS
2. OK FINAL FOR POWER IN MACHINE SHOP RM 124
3. DOWN DRAFT HOODS MISSING CONNECTORS, NOT GROUNDED PROPERLY, RECEPTACLES NOT SUPPORTED PROPERLY, MISSING STRAPS ON EMT - GSE HOODS
4. OK FINAL FOR POWER RM 127A, 127 & OTHER AREAS AS INDICATED ON PLANS
5. OK WALLS AS INDICATED ON PLANS.
11/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*