Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS TOOL CHASE #135 & #134 |
|
| 03/03/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 02/27/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK LIGHTING CONTROL PANELS 2. OK BOILERS AND HWP#1 AND HWP#2 3. OK CEILINGS RMS 107 & SOUTHEAST FIRST FLOOR UNDER MEZZANINE |
|
| 02/25/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
| 02/22/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/21/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CEILINGS 2ND FLOOR CONFERENCE ROOM 228 |
|
| 02/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DATA INSTALLED ABOVE DROP CEILINGS 2ND FLOOR OFFICE AREA |
|
| 02/01/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS RMS 100, 101, 102, 106, 104, 103, 228 2. OK CEILINGS HARD LIDS RMS 100 |
|
| 01/30/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK POLE BASE NORTH END OF PARKING LOT 2. OK PVC UNDER SLAB TO RECEPTION DESK 3. OK PVC UNDER SLAB IN CONFERENCE ROOM OFF OF RECEPTION 4. OK WALLS IN STAIRWELL @ RECEPTION 5. OK WIRING TO DISCONNECTS & CONTROL CABINETS FOR CDS 3, 4, 5, 6 AND 7 |
|
| 01/28/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/25/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER OUTSIDE WEST WALL |
|
| 01/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. OK WEST OUTSIDE WALL TO COLUMN LINE G 2. OK WALLS TOOL CHASE RM 133 3. OK WALLS RM 201A, 202 |
|
| 01/18/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 01/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALL @ LOADING DOCK 2. OK WALL @ MAIN RECEPTION 3. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF XFMR ET-13 AND PANEL PP2A 4. INSTALL PROTECTIVE BUSHING ON SECONDARY FOR XFMR ET-13 |
|
| 01/16/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. DATA WIRING TO BE SUPPORTED EVERY 6' MIN. HAVE CUT PROTECTIVE BUSHING ON 4" EMT FOR DATA 2. OK LIGHTS AND POWER WIRING 201E 3. OK HARD LID RM 212 |
|
| 01/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL RP2AA 2. OK WALLS RM 212, 201E, 209, 207 |
|
| 01/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK OUTDOOR WEST WALL TO COLUMN LINE C 2. OK WALLS RM 114, 114A, 210, 208, 206, 205, 204, 203 |
|
| 01/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MAKE PROPER GROUND CONNECTIONS IN DISCONNECTS AND JUNCTION BOXES NORTH PENTHOUSE |
|
| 01/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK LIGHTS 2ND FLOOR RM 221A, 221, 219, 218, 217, 216, 215, 214, 213, 211 - NEED TO CHECK FIRE ALARM & DATA WHEN INSTALLED 2. OK WALLS RM 212 |
|
| 01/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL PP1G, PDRP2B 2. OK DISCONNECT FOR XFMR T-12 |
|
| 01/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL PP2F, PP2H, RP2F 2. OK FEEDER TO DISCONNECT CIGS #11 3. OK PARTIAL FINAL 1ST FLOOR NORTH TO COLUMN LINE D EXCEPT WEST WALL |
|
| 01/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 01/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANELS PP2E, RP2EB, RP2E, PP2B, RP2GA, RP2H, RP2G, RP2D 2. OK DISCONNECT & FEEDER FOR MON DRAGON |
|
| 12/28/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 12/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PANELS PDP4A, ERP3B, GL3B, PDP2D, PDP 2B 2) OK FEEDER FOR CONVEYOR OVEN |
|
| 12/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) STARTED FINALS FOR 1ST FLOOR FROM COLUMN ? D 2) MAKE CORRECTIONS AS DISCUSSED |
|
| 12/21/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY CONTRACTOR |
|
| 12/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL PDP40, LDP2A, PDP2A, PDP2C 2. OK TRANSFORMER T2 |
|
| 12/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL PDP2E, PDRP2A, PDRP2B 2. OK TRANSFORMER T-3, T-4, T-12 3. REMOVE OLD & ABANDONED WIRING FROM SOUTH MEZZANINE |
|
| 12/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL RP1E, RP1D 2. OK DISCONNECT & PANEL FOR TCO #1, TCO #2 3. OK PROTECTIVE BUSHINGS FOR PANEL PP1H, PP1B 4. OK DOWN DRAFT HOODS (CORRECTIONS MADE) |
|
| 12/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL RP1F, PDP3C, PDP1B 2. OK TRANSFORMER T1, T8 |
|
| 12/14/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 12/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PANEL PDP1F & PDP1A SUPPORT RACEWAYS INTO THESE PANELS |
|
| 12/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PANEL PDP1E, PDP1C, PDP1D, PDP3E, EPP3A, PP1J, PP1, EL3A, LP3B 2. OK CEILING IN DATA CENTER 222B. SEAL OPEN ENDS OF SPARE RACEWAYS INTO PANEL 3. DATA CENTER 222B NEEDS TO MEET REQUIREMENTS OF NEC 645 |
|
| 12/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS RMS 113, 112, 111, 114 AS INDICATED ON PLANS 2. OK CEILINGS RMS 110, 109 3. OK PANEL PP1E |
|
| 12/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 12/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CONNECT GROUNDING ELECTRODE CONDUCTOR FOR XFMR T-8 TO ELECTRODE 2. INSTALL 60 AMP FUSES ON SECONDARY SIDE OF XFMR T-8 3. OK TO ENERGIZE PANEL RP5A 4. OK CEILINGS RM 125, 126 & HALLWAY OUTSIDE THESE ROOMS. |
|
| 11/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE PANELS PP2G & PDP2F |
|
| 11/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOMS 108, 109, 110 |
|
| 11/21/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 11/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOM #115 |
|
| 11/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOMS 221, 221A |
|
| 11/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK EAST OUTSIDE WALL 1ST FLOOR COLUMN LINE D TO F 2. OK CEILING ROOM 120 3. OK WALLS 2ND FLOOR RM 201 G |
|
| 11/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK CEILING IN TOOL CHASE RM 132 LEAVE TILES OPEN WHERE FIRE ALARM BOXES LOCATED 2. OK WALLS SECOND FLOOR RMS 211, 213, 214, 215, 216, 217, 218, 219, 220 |
|
| 11/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK CEILINGS IN BATHROOMS 1ST FLOOR RM #121, 123 2. OK WALLS RM #119 3. OK TO ALLOW TEMPORARY OCCUPATION OF RMS #127, 127A, 128 BY TECHNICAL PERSONNEL FOR TESTING OF EQUIPMENT PROVIDE LETTER FOR TEST OF EMERGENCY GENERATOR AND LIGHTING FOR THESE ROOMS. |
|
| 11/02/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS AS INDICATED ON DRAWINGS FOR 1ST FLOOR RMS 120, 124 2. ENSURE MC CABLE STRAPPED PROPERLY NEED MIN 1 1/4" BACK FROM STUDS |
|
| 10/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/25/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/19/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 10/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS RMS 132, 130, 125 2. OK WALL EAST FROM COLUMN LINE A TO D 3. NEED TO PROVIDE DEDICATED EQUIPMENT SPACE ABOVE SUB-STATION #1 PER NEC 110.26 (F)(1) |
|
| 10/15/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS ROOMS 125, 126, 121, 123, 131 2. ENSURE MC CABLES SECURED WITHIN 12" OF BOX 3. SECURE MC CABLES EVERY 6' 4. NEED 1 1/4" CLEARANCE FROM FACE OF STUDS |
|
| 10/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FEEDERS TO CA-01, CA-02 2. OK FEEDERS TO DRY-1, DRY-2 3. OK LIGHTING IN CONDENSING UNIT AREA 12 FIXTURES ROUGH ONLY 4. OK FEEDERS TO CH-1 & CH-2 |
|
| 10/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK FEEDER TO MCC 5A 2. OK FEEDER TO PP 5A 3. OK FEEDER TO EPP3 4. OK FEEDERS TO CHWP-1, CHWP-2, CWP-1, CWP-2 |
|
| 10/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | RECEIVED LETTER FROM ENGINEER & GE CONCERNING FENCE REQUIREMENTS AROUND 13.8 KV SUBSTATION IT APPEARS CONSTRUCTION OF SUBSTATION MEETS REQUIREMENTS OF NEC 110.31 & REQUIRES NO FENCE |
|
| 10/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL FAR SIDE SUPPORT ON BOXES FOR RECEPT/SWITCHES 2. OK WALLS 2ND FLOOR NORTH |
|
| 09/27/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK SOUTH WALL OF CDS ROOM 2) OK FEEDER TO PPIG 3) OK EMT ROUGH IN PENT HOUSE NORTH ROOF LEVEL |
|
| 09/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK SOUTH WALLS OF CDS ROOM LEAVE SECTION OPENS AT PANEL LOCATIONS 2. RECEIVED LETTER OF TORQUE FOR SWITCHGEAR |
|
| 09/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS CDS ROOM EXCEPT SOUTH WALLS WHERE PANELS ARE LOCATED |
|
| 09/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK SUBSTATION #5 TO ENERGIZE 2. PROVIDE LETTER OF TORQUE FOR SUBSTATION #5 & SUBSTATION #1 3. OK 4" RIGID TO EPP3 4. INSTALL GROUNDING ELECTRODE CONDUCTOR FOR LIDS 5. OK TO ENERGIZE SUB-STATION #1 6. PROJECT WILL NOT BE FINALED UNTIL ALL OLD PIPING AND WIRING IS REMOVED. |
|
| 08/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 1 1/2" EMT TO PANEL RP1E, OK 2 1/2" EMT TO PANEL URP1A, OK 2" EMT TO PANEL RP2D, OK 2" EMT TO PANEL RP2B AND OK 2" EMT TO DISCONNECTS ENVIORMENTAL CHAMBER, TC 133, TC 132 AND TC 131 |
|
| 08/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK 4" EMT(2) TO PDP2F 2. OK 4" EMT(2) TO PDP2E 3. OK 3" EMT(2) TO PP2C STRAP EMT WITHIN 3' OF PANEL 4. OK 4" EMT(2) TO PDP3C 5. OK 4" EMT(2) TO PDP3D 6. OK 4" EMT(2) TO PDP1A 7. OK 4" EMT(2) TO PDP3E 8. OK 4" EMT(2) TO PDP1F 9. OK 4" EMT(2) TO PDP1E 10. OK 4" EMT(2) TO PDP1C 11. OK 4" EMT(2) TO PDP1D 12. OK 5" RIGID (2) TO SUB-STATION #5 13. OK GROUNDING ELECTRODES AT SUB-STATION #5 |
|
| 08/03/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* MEETING TO DISCUSS PROJECT |