Permit: T07CM02315

Parcel: 14122004G


Addresses:

8500 S RITA RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/20/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS TOOL CHASE #135 & #134
03/03/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/27/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK LIGHTING CONTROL PANELS
2. OK BOILERS AND HWP#1 AND HWP#2
3. OK CEILINGS RMS 107 & SOUTHEAST FIRST FLOOR UNDER MEZZANINE
02/25/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
02/22/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CEILINGS 2ND FLOOR CONFERENCE ROOM 228
02/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DATA INSTALLED ABOVE DROP CEILINGS 2ND FLOOR
OFFICE AREA
02/01/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS RMS 100, 101, 102, 106, 104, 103, 228
2. OK CEILINGS HARD LIDS RMS 100
01/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK POLE BASE NORTH END OF PARKING LOT
2. OK PVC UNDER SLAB TO RECEPTION DESK
3. OK PVC UNDER SLAB IN CONFERENCE ROOM OFF OF RECEPTION
4. OK WALLS IN STAIRWELL @ RECEPTION
5. OK WIRING TO DISCONNECTS & CONTROL CABINETS FOR CDS 3, 4, 5, 6 AND 7
01/28/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/25/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER OUTSIDE WEST WALL
01/23/2008 ELECTRIC - INTERMEDIATE Partial Approval 1. OK WEST OUTSIDE WALL TO COLUMN LINE G
2. OK WALLS TOOL CHASE RM 133
3. OK WALLS RM 201A, 202
01/18/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
01/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALL @ LOADING DOCK
2. OK WALL @ MAIN RECEPTION
3. DO NOT HAVE PROPER WORKING CLEARANCE IN FRONT OF XFMR ET-13 AND PANEL PP2A
4. INSTALL PROTECTIVE BUSHING ON SECONDARY
FOR XFMR ET-13
01/16/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DATA WIRING TO BE SUPPORTED EVERY 6' MIN.
HAVE CUT PROTECTIVE BUSHING ON 4" EMT FOR DATA
2. OK LIGHTS AND POWER WIRING 201E
3. OK HARD LID RM 212
01/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL RP2AA
2. OK WALLS RM 212, 201E, 209, 207
01/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK OUTDOOR WEST WALL TO COLUMN LINE C
2. OK WALLS RM 114, 114A, 210, 208, 206, 205, 204, 203
01/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MAKE PROPER GROUND CONNECTIONS IN DISCONNECTS AND JUNCTION BOXES NORTH PENTHOUSE
01/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK LIGHTS 2ND FLOOR RM 221A, 221, 219, 218, 217, 216, 215, 214, 213, 211 - NEED TO CHECK FIRE ALARM & DATA WHEN INSTALLED
2. OK WALLS RM 212
01/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL PP1G, PDRP2B
2. OK DISCONNECT FOR XFMR T-12
01/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL PP2F, PP2H, RP2F
2. OK FEEDER TO DISCONNECT CIGS #11
3. OK PARTIAL FINAL 1ST FLOOR NORTH TO COLUMN LINE D EXCEPT WEST WALL
01/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANELS PP2E, RP2EB, RP2E, PP2B, RP2GA, RP2H,
RP2G, RP2D
2. OK DISCONNECT & FEEDER FOR MON DRAGON
12/28/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PANELS PDP4A, ERP3B, GL3B, PDP2D, PDP 2B
2) OK FEEDER FOR CONVEYOR OVEN
12/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) STARTED FINALS FOR 1ST FLOOR FROM COLUMN ? D
2) MAKE CORRECTIONS AS DISCUSSED
12/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY CONTRACTOR
12/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL PDP40, LDP2A, PDP2A, PDP2C
2. OK TRANSFORMER T2
12/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL PDP2E, PDRP2A, PDRP2B
2. OK TRANSFORMER T-3, T-4, T-12
3. REMOVE OLD & ABANDONED WIRING FROM SOUTH MEZZANINE
12/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL RP1E, RP1D
2. OK DISCONNECT & PANEL FOR TCO #1, TCO #2
3. OK PROTECTIVE BUSHINGS FOR PANEL PP1H, PP1B
4. OK DOWN DRAFT HOODS (CORRECTIONS MADE)
12/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL RP1F, PDP3C, PDP1B
2. OK TRANSFORMER T1, T8
12/14/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK PANEL PDP1F & PDP1A
SUPPORT RACEWAYS INTO THESE PANELS
12/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANEL PDP1E, PDP1C, PDP1D, PDP3E, EPP3A, PP1J, PP1, EL3A, LP3B
2. OK CEILING IN DATA CENTER 222B. SEAL OPEN ENDS OF SPARE RACEWAYS INTO PANEL
3. DATA CENTER 222B NEEDS TO MEET REQUIREMENTS OF NEC 645
12/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS RMS 113, 112, 111, 114 AS INDICATED ON PLANS
2. OK CEILINGS RMS 110, 109
3. OK PANEL PP1E
12/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CONNECT GROUNDING ELECTRODE CONDUCTOR FOR
XFMR T-8 TO ELECTRODE
2. INSTALL 60 AMP FUSES ON SECONDARY SIDE OF XFMR T-8
3. OK TO ENERGIZE PANEL RP5A
4. OK CEILINGS RM 125, 126 & HALLWAY OUTSIDE THESE ROOMS.
11/28/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE PANELS PP2G & PDP2F
11/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS 108, 109, 110
11/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
11/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOM #115
11/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS 221, 221A
11/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK EAST OUTSIDE WALL 1ST FLOOR COLUMN LINE D TO F
2. OK CEILING ROOM 120
3. OK WALLS 2ND FLOOR RM 201 G
11/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CEILING IN TOOL CHASE RM 132 LEAVE TILES OPEN WHERE FIRE ALARM BOXES LOCATED
2. OK WALLS SECOND FLOOR RMS 211, 213, 214, 215, 216, 217, 218, 219, 220
11/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CEILINGS IN BATHROOMS 1ST FLOOR RM #121, 123
2. OK WALLS RM #119
3. OK TO ALLOW TEMPORARY OCCUPATION OF RMS #127, 127A, 128 BY TECHNICAL PERSONNEL FOR TESTING OF EQUIPMENT
PROVIDE LETTER FOR TEST OF EMERGENCY GENERATOR AND LIGHTING FOR THESE ROOMS.
11/02/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS AS INDICATED ON DRAWINGS FOR 1ST FLOOR
RMS 120, 124
2. ENSURE MC CABLE STRAPPED PROPERLY NEED MIN 1 1/4" BACK FROM STUDS
10/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
10/25/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/19/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
10/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS RMS 132, 130, 125
2. OK WALL EAST FROM COLUMN LINE A TO D
3. NEED TO PROVIDE DEDICATED EQUIPMENT SPACE ABOVE SUB-STATION #1 PER NEC 110.26 (F)(1)
10/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS ROOMS 125, 126, 121, 123, 131
2. ENSURE MC CABLES SECURED WITHIN 12" OF BOX
3. SECURE MC CABLES EVERY 6'
4. NEED 1 1/4" CLEARANCE FROM FACE OF STUDS
10/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK FEEDERS TO CA-01, CA-02
2. OK FEEDERS TO DRY-1, DRY-2
3. OK LIGHTING IN CONDENSING UNIT AREA 12 FIXTURES
ROUGH ONLY
4. OK FEEDERS TO CH-1 & CH-2
10/08/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK FEEDER TO MCC 5A
2. OK FEEDER TO PP 5A
3. OK FEEDER TO EPP3
4. OK FEEDERS TO CHWP-1, CHWP-2, CWP-1, CWP-2
10/05/2007 ELECTRIC - INTERMEDIATE Partial Approval RECEIVED LETTER FROM ENGINEER & GE CONCERNING FENCE REQUIREMENTS AROUND 13.8 KV SUBSTATION
IT APPEARS CONSTRUCTION OF SUBSTATION MEETS REQUIREMENTS OF NEC 110.31 & REQUIRES NO FENCE
10/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL FAR SIDE SUPPORT ON BOXES FOR RECEPT/SWITCHES
2. OK WALLS 2ND FLOOR NORTH
09/27/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK SOUTH WALL OF CDS ROOM
2) OK FEEDER TO PPIG
3) OK EMT ROUGH IN PENT HOUSE NORTH ROOF LEVEL
09/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SOUTH WALLS OF CDS ROOM LEAVE SECTION OPENS AT PANEL LOCATIONS
2. RECEIVED LETTER OF TORQUE FOR SWITCHGEAR
09/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS CDS ROOM EXCEPT SOUTH WALLS WHERE PANELS ARE LOCATED
09/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK SUBSTATION #5 TO ENERGIZE
2. PROVIDE LETTER OF TORQUE FOR SUBSTATION #5 & SUBSTATION #1
3. OK 4" RIGID TO EPP3
4. INSTALL GROUNDING ELECTRODE CONDUCTOR FOR LIDS
5. OK TO ENERGIZE SUB-STATION #1
6. PROJECT WILL NOT BE FINALED UNTIL ALL OLD PIPING AND WIRING IS REMOVED.
08/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 1 1/2" EMT TO PANEL RP1E, OK 2 1/2" EMT TO PANEL URP1A, OK 2" EMT TO PANEL RP2D, OK 2" EMT TO PANEL RP2B AND OK 2" EMT TO DISCONNECTS ENVIORMENTAL CHAMBER, TC 133, TC 132 AND TC 131
08/15/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK 4" EMT(2) TO PDP2F
2. OK 4" EMT(2) TO PDP2E
3. OK 3" EMT(2) TO PP2C STRAP EMT WITHIN 3' OF PANEL
4. OK 4" EMT(2) TO PDP3C
5. OK 4" EMT(2) TO PDP3D
6. OK 4" EMT(2) TO PDP1A
7. OK 4" EMT(2) TO PDP3E
8. OK 4" EMT(2) TO PDP1F
9. OK 4" EMT(2) TO PDP1E
10. OK 4" EMT(2) TO PDP1C
11. OK 4" EMT(2) TO PDP1D
12. OK 5" RIGID (2) TO SUB-STATION #5
13. OK GROUNDING ELECTRODES AT SUB-STATION #5
08/03/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
MEETING TO DISCUSS PROJECT