Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/02/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* PLAN DOES NOT SHOW "FUNNEL DRAIN" OR WATER HEATER T&P RELIEF DRAIN OR TRAP PRIMER, WET VENTED BELOW KITCHEN SINK DRAIN. BESIDES, MINIMUM WASTE SIZE FOR KITCHEN SINK IS 2" SO WET VENTED SECTION AND ALL WASTE PIPING WOULD HAVE TO BE 3" - AND THAT IS NOT THE WAY IT IS INSTALLED. ALSO, A NO-HUB BELL REDUCER IS NOT AN APPROVED INDIRECT WASTE RECEPTACLE. |