Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. LETTER CONCERNING OMISSION OF OCCUPANCY SENSORS TO COME FROM ELEC. ENGINEER OF RECORD 2. NUMBER BREAKERS OK TO OCCUPY SPACE |
|
| 08/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN SHOWS OCCUPANCY SENSORS FOR LIGHTING 2. NEED GFI PROTECTION FOR RECEPTACLE @ RIGHT OF SINK (PER PLAN) 3. IDENTIFY CKT'S PROPERLY ON PANEL SCHEDULE IN PANEL DOOR -- NEC 408.4 |