Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM02272

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/25/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/23/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC STILLN OT PROPERLY SUPPORTED - CAN'T LAY ON DUCT WORK SUPPORT AT PROPER INTERVALS, STRAP WITHIN 12" OF TERMINATIONS NEC 320.30
2. STILL HAVE OVERFILLED, UNGROUNDED J-BOXES,
NEC 314.16, NEC 314.4
3. SECURE EMT WITHIN 36" OF ENCLOSURES - NEC 358.30A
4. SECURE SUPPORT WIRES @ 2 ENDS -- NEC 300.11

CHECK ALL RACEWAY SUPPORT
REFEE IF NOT CORRECT NEXT TIME
07/19/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED
07/16/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION, CHECK ALL RACEWAY STRAPPING,
PROPERLY SUPPORT J-BOXES
SUPPORT WIRES TO BE SECURED AT BOTH ENDS

1. REMOVE ANY ABANDONED LOW VOLTAGE WIRING
2. SEAL UNUSED OPENINGS IN BOXES
3. GROUND ALL J-BOXES
4. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
5. USE MC STRAPS, NOT 1/2" EMT STRAPS
6. GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT WIRING
7. RACEWAYS NOT TO BE USED TO SUPPORT OTHER RACEWAYS OR CABLES
8. HAVE OVERFILLED BOXES -- CHECK AND ADD EXTENSIONS AS NEEDED
07/12/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/09/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/21/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
PHASE ONE CEILING
1. SUPPORT WIRES FOR MC TO BE SECURED @ BOTH ENDS
(SECURE OTHER END TO GRID) - NEC 300.11

OK TILES AFTER THAT