Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RING -- 314.20 2. EM & EXIT LIGHTING TO BE ON CIRCUIT FOR AREA SERVED -- 700.12 3. LABEL BREAKERS AS PER 408.4 4. CORRECTLY GROUND BATH LIGHTS |