Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM01984
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/15/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR TEMP POWER FOR TEST-SUBJECT TO BOND |
|
06/13/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL UNUSED OPENINGS IN BOXES NEC 300 2) SECURE MC PER NEC 330.30 3) REMOVE LOW VOLTAGE WIRING NOT USED NEC 800 4) SECURE FIXTURES TO GRID ADD SUPPORT WIRES NEC 300.11 5) HAVE OVERFILLED J-BOXES NEC 314.16 |