Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/24/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ACCESS. DOORS LOCKED. |
|
| 04/16/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDENSATE UNITS OVER FUSED AND UNDER FUSED 2. GUARD AROUND CONDENSORS DOES NOT ALLOW ACCESS TO ELECTRICAL PANEL 3. ALL PVC PIPING TO HAVE PRIMER AT ALL JOINTS (PURPLE) 4. PROVIDE SECONDARY DRAIN ON INDOOR UNITS 5. INDOOR UNIT DATA PLATE IS NOT READABLE, UNABLE TO DETERMINE FUSE REQUIREMENTS 6. UPSTAIRS INDOOR UNIT DATA PLATE NOT IDENTIFIED FOR FUSE REQUIREMENTS 7. PROVIDE FILTERS FOR INDOOR UNITS 8. PROVIDE ACCESS TO ROOF 9. PROVIDE AIR BALANCE REPORT PER PLANS |