Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/20/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO WORK ON CORRECTIONS DONE REFEE APPLIED TO THE ACTIVITY |
|
| 10/15/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MECHANICALLY FASTEN THE EXHAUST DUCTS TO THE FAN AND TO WALL TERMINAL 2. PROVIDE PRIMER ON ALL PVC CONDENSATE FITTINGS PRIOR TO GLUE 3. INSULATE 4 SIDE WALL REGISTER BOXES. 4. SEAL DOVE TAIL 2ND FLOOR 5. PROVIDE BACKING AROUND SIDE WALL REGISTER BOX IN RESTROOM & 2ND FLOOR CEILING BOX 6. PLEASE REVISE PLANS TO SHOW THE PROPER DUCT SYSTEM AND AC UNIT FOR 2ND FLOOR 7. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 8. INSULATE CEILING BOX 2ND FLOOR 9. COMBUSTIBLE MATERIAL NOT ALLOWED IN A RETURN PLENUM IN A COMMERCIAL BLDG. 10. PROVIDE SCREENS IN ANY ROOFTOP RELIEF VENTS 11. ROOF ACCESS NOT PER PLAN |