Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2009 | PLUMBING - FINAL | Approved | PLAN CHANGES ACCEPTED FOR AS-BUILT CONDITIONS. CLEAN BACTERIA REPORT ACCEPTED. | |
| 04/28/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WALK THRU WITH MIKE FROM BEST WAY 2. SOME CHANGES HAVE BEEN MADE - MAKE ALL CORRECTIONS I WILL REQUIRE AN APPROVED REVISED PLAN FOR FINAL |
|
| 04/24/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PER NOTE NUMBER ONE FROM 1/12/09 PLUMBING ALTERED AND COVERED W/O INSPECTION 2. EWC INSTALLATION NOT APPROVED. SEE NOTES #2 & #3 FROM 1/12/09 3. NO EXPANSION TANK AT WATER HEATER 4. NO MIXING VALVES AT LAVATORIES 5. NOT INSTALLED PER PLAN I.E. FIXTURES, SUPPLIES, ANGLE STOPS, ETC. 6. REQUIRE ELONGATED BOWL WITH OPEN FRONT SEATS AT WATER CLOSETS 7. REQUIRE AVB's AT HOSE BIBS 8. REQUIRE STERILIZATION OF WATER PIPING REQUIRE CLEAN BACTERIA REPORT 9. NO NOTICE IN ELECTRIC SERVICE PANEL |