Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2008 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* ALL PIPING EXPOSED TO CONCRETE TO BE WRAPPED CALL 03015 FOR PRE-SLAB INSPECTION |
|
| 06/25/2008 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/10/2008 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE APPROVED SITE UTILITY PLAN, INCLUDING ACCEPTABLE MATERIAL TYPES 2. IF YOU ARE USING THE HOSE BIB, INSTALL AVB IMMEDIATELY 3. F.I.P ADPTS ON PVC NOT APPROVED WITH METALLIC MALE THREADS 4. ROUGH IN NOT INSTALLED PER PLAN - NO REDLINES ON SITE 5. RE-READ NOTE #6 FROM 06/04/08 6. NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED 7. ABS MAY NOT BE DIRECTLY EMBEDDED IN CONCRETE 8. NO HUB BANDS ARE LISTED TO BE USED WITH CAST IRON 9. USE THE CORRECT TRANSITION COUPLINGS AT P.O.C TO EXISTING |