| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/27/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* * A BOND WILL BE NEEDED FOR POWER * ALSO, HAVE OLD INSPECTIONS ON SITE 1. PLEASE PROVIDE A MEGGAR REPORT ON CONDUCTOR INSULATION INTEGRITY DUE TO DAMAGES TO INSULATION 2. L.B. MAX CONDUCTOR SIZE 4/0 - HAVE 600 KEMU 3. SEAL ENTRANCES ABOVE CURRENT CARRING PARTS WITH APPROVED DEVICES 4. INSTALL MAIN BONDING JUMPER 5. VERIFY WATER & GAS BONDING 6. PLEASE VERIFY SUB-PANEL RATINGS OF 22K ALSO, BREAKERS NEED TO VERIFY SERIES RATING |