Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST FLOOR/2ND FLOOR ROUGH ELECTRIC TO DRYWALL RECEIVED MONEY ORDER #68254689030 -- $150.00 |
|
| 11/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | OK 1/0 TO 2 GROUND RODS OK 2ND FLOOR ONLY 1. OUTLETS NOT AS PER PLANS 2. A/C NOT AS PER PLANS 3. SUPPORT LOW VOLTAGE (VDV) CABLING IN WALLS - 725.24 4. INSTALL FAN RATED BOXES FOR CEILING FANS 5. INSTALL PHONE AND CABLE SMART PANEL 6. CONDUITS UNDER DRIVEWAY TO BE AS PER 300.5 (24") 7. FINISH SERVICE AS PER PLANS |
|
| 11/12/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* MUST HAVE PLANS AND INSPECTION BY BUILDING INSPECTOR FIRST |
|
| 10/29/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO WORK PROGRESS |
|
| 10/20/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. UNCOVER UNDERGROUND TO INSPECT FOR A/C's 2. SERVICE NIPPLE TO BE BONDED PER 250.92 3. ITEMS #1, 2 & 5 NOT COMPLETE |
|
| 10/15/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ELECTRIC EQUIPMENT PANELS & SERVICE NOT AS PER PLANS 2. UFER NOT INSPECTED AS PER 250.50 & 64 3. USE APPROVED M/C CONNECTORS 4. IS EM/EXIT LIGHTING AS PER 700.12(F)? 5. HAVE BUILDING INSPECTOR VERIFY DAMAGE TO TGI's 6. PROPERLY SUPPORT M/C & WITHIN 12" OF BOXES, EXHAUST FANS, PANELS 7. FILL UNUSED OPENINGS IN BOXES 8. WHERE IS ELECTRIC FOR AC's? |