Permit: T07CM01348

Parcel: 106030550


Addresses:

3232 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/31/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1ST FLOOR/2ND FLOOR
ROUGH ELECTRIC TO DRYWALL

RECEIVED MONEY ORDER #68254689030 -- $150.00
11/18/2008 ELECTRIC - INTERMEDIATE Partial Approval OK 1/0 TO 2 GROUND RODS
OK 2ND FLOOR ONLY

1. OUTLETS NOT AS PER PLANS
2. A/C NOT AS PER PLANS
3. SUPPORT LOW VOLTAGE (VDV) CABLING IN WALLS - 725.24
4. INSTALL FAN RATED BOXES FOR CEILING FANS
5. INSTALL PHONE AND CABLE SMART PANEL
6. CONDUITS UNDER DRIVEWAY TO BE AS PER 300.5 (24")
7. FINISH SERVICE AS PER PLANS
11/12/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
MUST HAVE PLANS AND INSPECTION
BY BUILDING INSPECTOR FIRST
10/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
10/20/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. UNCOVER UNDERGROUND TO INSPECT FOR A/C's
2. SERVICE NIPPLE TO BE BONDED PER 250.92
3. ITEMS #1, 2 & 5 NOT COMPLETE
10/15/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ELECTRIC EQUIPMENT PANELS & SERVICE
NOT AS PER PLANS
2. UFER NOT INSPECTED AS PER 250.50 & 64
3. USE APPROVED M/C CONNECTORS
4. IS EM/EXIT LIGHTING AS PER 700.12(F)?
5. HAVE BUILDING INSPECTOR VERIFY DAMAGE TO TGI's
6. PROPERLY SUPPORT M/C & WITHIN 12" OF BOXES, EXHAUST FANS, PANELS
7. FILL UNUSED OPENINGS IN BOXES
8. WHERE IS ELECTRIC FOR AC's?