| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED CK#008059000 - $300.00 1. LABEL A/C DISCONNECTS 2. SPLICES TO BE FOR WET LOCATION |
|
| 06/03/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ELECTRIC ROOM: 1. GROUNDED CONDUCTORS ATTACHED TO BREAKERS 2. FINISH PANEL SCHEDULES 408.4 LAUNDRY ROOM: 1. SEPARATE GROUNDED AND GROUNDING CONDUCTOR AT DISCONNECTS 250.24 2. LABEL DISCONNECTS 3. BOND ENCLOSURES 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 5. BOND PANEL ENCLOSURE 6. FIXTURES TO HAVE DISCONNECTING MEANS 410.63 AND GROUND FIXTURES RISER ROOM: 1. USE APPROVED FITTINGS WITH M/C CABLE 2. FILL UNUSED OPENINGS IN BOXES 3. HEATER NOT AS PER PLANS NEED DISCONNECTING MEANS |
|
| 06/02/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 05/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* KITCHEN: 1. ALL RECEPTACLES IN KITCHEN TO BE GFCI PROTECTED 210.8(B) OK BUFFET LINE OK BOLLARD LIGHTING OUTSIDE LIGHTS: 1. PROPERLY BOND POLE LIGHTS 2. PULL BOXES TO BE LISTED FOR ELECTRIC 3. SPLICES TO BE FOR WET LOCATION 4. USE APPROVED HARDWARE WALL LIGHTS |
|
| 05/26/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ATTIC 3RD FLOOR - DONE 2ND FLOOR - FINISH LABELING, RECEPTACLE FOR HALL BUILDING INSPECTOR TO DETERMINE LOW EXIT SIGN REQUIREMENTS - IF ELECTRIC IS INSTALLED, NEEDS INSPECTIONS. |
|
| 05/22/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FIRE ALARM PANEL UL LABEL ADDED IN FIELD CANNOT BE FIELD LABELED BY OTHER THAN UL 2. PLAN REVISION FOR SWITCHING TO BE STAMPED BY CITY FRONT SOFFIT 1. LABEL DISCONNECT 2. PROTECT CONDUCTORS 300.4 3. TIGHTEN LOOSE FITTINGS 4. STRAP NM CABLE OUTSIDE AC's 1. BOND ENCLOSURES 2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 3. LABEL DISCONNECTS 4. REINSTALL DOOR 5. TIGHTEN LOOSE FITTINGS OK RECEPTION COUNTER 181, WORK AREA 182, OFFICES 183, 184, RESTROOMS 171, 172 BUSINESS LTR 164, EXERCISE 166, STORAGE 169, LOUNGE 167 BREAKFAST 176, LOBBY 178 |
|
| 05/21/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) #103 CIRCUITS NOT PER PANEL SCHEDULE 2) #134 LIGHT FIXTURE BOX 3) OK 1ST FLOOR GUEST ROOMS, EXCEPT AS NOTED |
|
| 05/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1ST FLOOR ROOMS: #106 SWITCHES FOR LIGHTING NOT WORKING #104 STRAP M/C UNDER COUNTER #102 MISSING BATH CAN, STRAP M/C UNDER COUNTER #101 PROPERLY GROUND LIGHT FIXTURE, BREAKER SCHEDULE NOT CORRECT |
|
| 05/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EXIT LIGHT DOWN LOW MISSING LOBBY FRONT DOOR AND BUFFET 2. VERIFY LISTING FIRE ALARM CONTROL PANEL 3. STRAP NM CABLE TO MAINTENANCE RECEPTACLE, NM TO BE 1/4" INTO BOX, FILL UNUSED OPENINGS |
|
| 05/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1ST FLOOR: 1) ENTRY VESTABLE NOT FINISHED 2) EXIT LIGHTS TO BE PER 700.12 (F) 3) GROUND UNDER CABINET LIGHTS AND SECURE CABLE TO FIXTURE 4) FINISH ATTIC AS DISCUSSED 5) OK 1ST FLOOR CORRIDOR ONLY 6) LIGHTING NOT SWITCHED PER PLANS |
|
| 05/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 2ND FLOOR 1. PLEASE VERIFY LISTING OF FIRE ALARM CONTROL PANELS 2. EXIT LIGHTS TO BE AS PER 700.12 3. LABEL A/C DISCONNECT 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 5. FINISH PANEL DIRECTORIES *WHERE IS CABLE ANTENNA GROUND 815 OR 820 OK 2ND FLOOR HALL 1. PLASTIC PULL BOXES TO BE LISTED |
|
| 05/11/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK ATTIC, 3RD FLOOR ROOMS AND HALLS, ASSOC. ROOMS 2ND FLOOR ROOMS ONLY 1. FINISH 2ND FLOOR HALLS |
|
| 05/08/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH 3RD FLOOR FOR NEXT INSPECTION |
|
| 05/07/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 2ND FLOOR EAST 1/2: 1. BOXES FOR LIGHT NOT ALLOWED OVER 6LBS. FOR SINGLE GANG 2. OUTSIDE LIGHTS NEED EXTENDER SHIELD AND GROUND HARD WIRE |
|
| 05/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 3RD FLOOR 1. NEED METAL BOX WITH M/C CABLE 2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS AT RANGE/COOKTOPS 3. FILL UNUSED OPENINGS IN PANEL FINISH PREVIOUS MARKED ITEMS |
|
| 05/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 3RD FLOOR 1. USE APPROVED HARDWARE WITH BOXES - NOT DRYWALL SCREWS OR SHEETMETAL SCREWS 2. BOX LOOSE IN WALL 3. MARKING TAPE TO ENCIRCLE CONDUCTORS 4. GROUND FIXTURE AND HARDWARE 5. INSTALL ALL STRANDS OF CONDUCTOR UNDER BREAKER TERMINALS ATTIC 1. FINISH ATTIC *IF WORK IS NOT PROGRESSING A REFEE MAY BE ASSESSED |
|
| 04/30/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 2ND FLOOR WALLS 1. SUPPORT VDV CABLING 725.24, 760.24, 800.24, 300.11 ATTIC: 1. FILL UNUSED OPENINGS IN BOXES 2. MAINTAIN ALL CLEARANCES PER 110.26 3. TIGHTEN LOOSE FITTINGS 4. LABEL DISCONNECTING MEANS 5. PROTECT NM CABLES ACROSS WALKWAYS 6. BOX MORE THAN FLUSH WITH FIXTURES 3RD FLOOR FINAL: 1. NO WORK PROGRESS 1. OK 1ST FLOOR HALLS ELECTRIC ABOVE CEILING 2. OK 2ND FLOOR HALLS ELECTRIC ABOVE CEILING AFTER CORRECTION 3. OK LOBBY, OFFICE, PREP ABOVE CEILING |
|
| 04/28/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ELECTRIC ROOM: 1. SEPARATE & SUPPORT NM & SE CABLES ABOVE PANELS 1ST FLOOR: CEILING 1. SUPPORT M/C CABLE PER CODES 2. GROUND JUNCTION BOX 3. MISSING BOX COVERS 3RD FLOOR ROOMS: FINAL 1. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM BOTTOM OF PANEL 2. COVER CANNOT SUPPORT RECEPTACLE 3. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE - 314.20 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 5. LABEL PANEL SCHEDULE AS PER 408.4 |