Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/04/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/28/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 04/22/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/17/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLOOR: 1. BOX OVERFILLED OUTSIDE ELECTRIC ROOM 2ND FLOOR: 1. SUPPORT M/C CABLE AS PER CODES 2. SUPPORT VDV CABLING 725.24, 800.24, 810.24, 815.24, 300.11 OK EXHAUST FAN 1ST FLOOR ELECTRIC ROOM OK PVC CONDUIT BOLLARD LIGHTING |
|
| 04/16/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/15/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 03/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SEE NOTES FOR AIR HANDLER |
|
| 03/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. TAG OUT LOCK OUT FOR ELECTRICAL EQUIP. 2. CONTR. TO INSURE THAT ONLY AUTHORIZED PERSONNEL TO HAVE ACCESS TO ELEC. EQUIP. ALL PANELS TO BE COVERED |
|
| 03/25/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO WORKING CLEARANCE FOR IN ROOM AIR HANDLERS J-BOX NOT ACCESSIBLE NEC 110-26 TOO SOON FOR TEMP POWER FOR TEST OK GAS BONDING (WATER PVC) |
|
| 03/17/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NEED TO TALK TO DAN ELECTRICAL INSPECTOR |
|
| 01/20/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER OF HARD LIDS |
|
| 01/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BATHROOM, CAN LIGHTS IN 2ND & 3RD FLOOR 3RD FLOOR HALLWAY FIRE RATED BOX & CAN LIGHTS AND LIGHTS OK |
|
| 11/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK GUEST ROOMS ROUGH 1ST, 2ND, 3RD, MAINT., LAUNDRY |
|
| 10/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3RD FLOOR ROUGH |
|
| 10/09/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS, CEILING AREAS THAT ARE ACCESSIBLE CANNOT BE RUN IN ROMEX PER 334.12 NCE. 171,172,178,180,181,182,183,184,175,173,165,176,162,163,164, 166,167,168,169,170,159,161,174,151,155,150,179 2) LIGHTING AND RECEPT REQUIRED AT AIR HANDLING EQUIP PER 210.70 & 210.63 |
|
| 10/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR LAUNDRY ROOM, STORAGE, PHONE RM. OK 3RD FLOOR MAINT. ROOM STORAGE |
|
| 09/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELEC. ONLY 3RD FLOOR WEST 1/2 LV. CABLING NOT IN YET |
|
| 09/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR EAST ELECTRICAL ONLY LV CABLING NOT IN YET |
|
| 09/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK FOR WALLS ELECTRICAL ONLY, LV CABLING NOT IN YET. 2ND FLOOR WEST |
|
| 09/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PARTIAL GUESTROOMS ELEC. ROUGH ONLY NO APPROVAL UNTIL LV CABLING IN EAST WING 1ST FLOOR AND WEST WING 1ST FLOOR EXCEPT PANELS |
|
| 09/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. AU FEEDERS 100 AMP OR GREATER APPROVED PER SEC 16120-2 ELECT. SPECS. 2. NM CABLE IN GUEST ROOMS ONLY 3. NEED ENGINEER APPROVAL FOR SER CABLE IN LIEU OF RACEWAY 4. ALL LV CABLING MUST BE INSTALLED IN WALLS & CEILING PRIOR TO APPROVAL |