Permit: T07CM01151

Parcel: 14042080C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/03/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/04/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/28/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/22/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/17/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR:
1. BOX OVERFILLED OUTSIDE ELECTRIC ROOM

2ND FLOOR:
1. SUPPORT M/C CABLE AS PER CODES
2. SUPPORT VDV CABLING 725.24, 800.24, 810.24, 815.24, 300.11

OK EXHAUST FAN 1ST FLOOR ELECTRIC ROOM
OK PVC CONDUIT BOLLARD LIGHTING
04/16/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/15/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
03/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEE NOTES FOR AIR HANDLER
03/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. TAG OUT LOCK OUT FOR ELECTRICAL EQUIP.
2. CONTR. TO INSURE THAT ONLY AUTHORIZED PERSONNEL TO HAVE ACCESS TO ELEC. EQUIP. ALL PANELS TO BE COVERED
03/25/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO WORKING CLEARANCE FOR IN ROOM AIR HANDLERS
J-BOX NOT ACCESSIBLE NEC 110-26
TOO SOON FOR TEMP POWER FOR TEST OK GAS BONDING (WATER PVC)
03/17/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NEED TO TALK TO DAN ELECTRICAL INSPECTOR
01/20/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK REMAINDER OF HARD LIDS
01/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BATHROOM, CAN LIGHTS IN 2ND & 3RD FLOOR
3RD FLOOR HALLWAY FIRE RATED BOX & CAN LIGHTS AND LIGHTS OK
11/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK GUEST ROOMS ROUGH 1ST, 2ND, 3RD, MAINT., LAUNDRY
10/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 3RD FLOOR ROUGH
10/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS, CEILING AREAS THAT ARE ACCESSIBLE CANNOT BE RUN IN ROMEX PER 334.12 NCE. 171,172,178,180,181,182,183,184,175,173,165,176,162,163,164, 166,167,168,169,170,159,161,174,151,155,150,179
2) LIGHTING AND RECEPT REQUIRED AT AIR HANDLING EQUIP PER 210.70 & 210.63
10/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND FLOOR LAUNDRY ROOM, STORAGE, PHONE RM.
OK 3RD FLOOR MAINT. ROOM STORAGE
09/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELEC. ONLY 3RD FLOOR WEST 1/2 LV. CABLING NOT IN YET
09/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 2ND FLOOR EAST ELECTRICAL ONLY LV CABLING
NOT IN YET
09/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PARTIAL OK FOR WALLS ELECTRICAL ONLY, LV CABLING NOT IN YET. 2ND FLOOR WEST
09/17/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PARTIAL GUESTROOMS ELEC. ROUGH ONLY
NO APPROVAL UNTIL LV CABLING IN
EAST WING 1ST FLOOR AND WEST WING 1ST FLOOR
EXCEPT PANELS
09/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. AU FEEDERS 100 AMP OR GREATER APPROVED PER
SEC 16120-2 ELECT. SPECS.
2. NM CABLE IN GUEST ROOMS ONLY
3. NEED ENGINEER APPROVAL FOR SER CABLE IN LIEU OF RACEWAY
4. ALL LV CABLING MUST BE INSTALLED IN WALLS & CEILING PRIOR TO APPROVAL