Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL MIXING VALVES AT LAVATORIES IN A WORKMANSHIP LIKE MANNER 2. PIPING HAS COME LOOSE IN THE WALL 3. PROVIDE LISTING FOR HAMMER ARRESTOR TO BE INSTALLED HORIZONTALLY |
|
| 06/16/2008 | PLUMBING - FINAL | Approved | IVRS - Inspection :* PLUMBING FINAL APPROVED BLDG FINAL APPROVED |
|
| 06/12/2008 | PLUMBING - FINAL | Not ready for Inspection | PLUMBER DIDN'T FOLLOW THE PLAN PLAN CALLS FOR: CAST BRASS P-TRAP CHROME PLATED LOOSE KEY ANGLE STOPS SIMMONS #5 - 120 THERMIXER WHERE IS THE A.D AND WATER HAMMER ARRESTOR? PLAN CALLS FOR A CLEAN OUT AT P-3 DO NOT ACTIVATE GAS UNTIL GIVEN PERMISSION BY INSPECTOR - MAY NOT BE A COMPLETE LIST |