Date Description Inspector Results Comments
06/13/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1. REMOVE SYSTEM BONDING JUMPER PANEL P3 -
NEC 250.30 A1
2. SERVER ROOM EMERGENCY LIGHT NOT WORKING
3. STAIRWELL EXIT SIGN NOT WORKING

TALK WITH ELECTRICAL CONTRACTOR AND HE WILL CORRECT