| 06/13/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. REMOVE SYSTEM BONDING JUMPER PANEL P3 - NEC 250.30 A1 2. SERVER ROOM EMERGENCY LIGHT NOT WORKING 3. STAIRWELL EXIT SIGN NOT WORKING TALK WITH ELECTRICAL CONTRACTOR AND HE WILL CORRECT |