Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/02/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL ITEMS FROM INSPECTION ON 3/28/08
03/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BONDING SCREWS A/C DISCONNECTS
2. AC UNIT OVERFUSED
3. PROPERLY WIRE EXHAUST FAN
4. USE WEATHERPROOF FITTINGS ON EMT FOR THERMOSTAT WIRING
5. USE APPROPRIATE FITTINGS FOR RACEWAYS
6. GET LOW VOLTAGE THEMOSTAT OUT OF AC DISCONNECT
7. INSTALL MOUNTING SCREWS FOR RECEPT IN INDUSTRIAL COVERS
8. BATHROOM RECEPTS TO BE GFI
9. DO NOT SEE LISTING MARK OR SCOREBOARD
10. WIRE DISHWASHER
11. FINISH FLOOR RECEPTS
12. EM LIGHTS NOT WORKING CHECK ALL
13. NEED LIGHTING IN GYM PER NEC 700.16