Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00943
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/02/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ALL ITEMS FROM INSPECTION ON 3/28/08 |
|
03/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING SCREWS A/C DISCONNECTS 2. AC UNIT OVERFUSED 3. PROPERLY WIRE EXHAUST FAN 4. USE WEATHERPROOF FITTINGS ON EMT FOR THERMOSTAT WIRING 5. USE APPROPRIATE FITTINGS FOR RACEWAYS 6. GET LOW VOLTAGE THEMOSTAT OUT OF AC DISCONNECT 7. INSTALL MOUNTING SCREWS FOR RECEPT IN INDUSTRIAL COVERS 8. BATHROOM RECEPTS TO BE GFI 9. DO NOT SEE LISTING MARK OR SCOREBOARD 10. WIRE DISHWASHER 11. FINISH FLOOR RECEPTS 12. EM LIGHTS NOT WORKING CHECK ALL 13. NEED LIGHTING IN GYM PER NEC 700.16 |