Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00943

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/28/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/27/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/21/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/18/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK HARD LIDS FOR LOCKER ROOMS. WILL NEED WALKWAY ABOVE CEILING FOR ACCESS TO JUNCTION BOXES
2. OK WALLS @ RECEPTION AREA
3. OK TO ENERGIZE KITCHEN PANEL
01/17/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
HARD LIDS
1. JUNCTION BOX ABOVE SHEETROCK CEILING NOT ACCESSIBLE
2. DROP TEMP LIGHTS BELOW GRID
3. NEED MORE SUPPORT ON RACEWAYS 3' FROM BOXES
AND 10' BETWEEN
4. JUNCTION BOXES NEED TO BE SUPPORTED