Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00943
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/28/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/27/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/21/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/18/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK HARD LIDS FOR LOCKER ROOMS. WILL NEED WALKWAY ABOVE CEILING FOR ACCESS TO JUNCTION BOXES 2. OK WALLS @ RECEPTION AREA 3. OK TO ENERGIZE KITCHEN PANEL |
|
01/17/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* HARD LIDS 1. JUNCTION BOX ABOVE SHEETROCK CEILING NOT ACCESSIBLE 2. DROP TEMP LIGHTS BELOW GRID 3. NEED MORE SUPPORT ON RACEWAYS 3' FROM BOXES AND 10' BETWEEN 4. JUNCTION BOXES NEED TO BE SUPPORTED |