Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - MEDICAL GAS/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2008 | PLUMBING - MEDICAL GAS/TEST | Approved | IVRS - Inspection :* | |
| 01/16/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* - PLAN REVISIONS - CACTUS MEDICAL - BACT. REPORT - HOSES ON TUBS REQUIRE BACKFLOW PROTECTION - FAUCETS ARE LISTED FOR RESIDENTIAL USE PROVIDE LISTING - LOOSE KEY STOPS SPECIFIED - ADDRESS ALL FIXTURE SPEC. CHANGES WITH A LETTER FROM EGLIN/COHEN - AERATORS LEAKING - CLIPS MISSING ON SINKS - 2 CLIPS MIN. ON ALL SIDES - PROVIDE EQUIPMENT TO BE INSTALLED IN RM 116 OR PERM CAP CONNECTIONS - P10'S NOT INSTALLED IN ALL LOCATIONS - P3 IN RM 112 MISSING MIXING VALVE - HAMMER ARRESTORS AT P-9 - CHECK FOR LEAKS (TEST ALL SINKS) - INSTALL PVC ADAPTOR AT AAV VTRS |
|
| 01/08/2008 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 01/07/2008 | PLUMBING - MEDICAL GAS/TEST | Cancelled | CANCELLED PER ALEX | |
| 09/13/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 09/12/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* | |
| 09/11/2007 | PLUMBING - MEDICAL GAS/TEST | Partial Approval | IVRS - Inspection :* MATERIAL CHECKED, PURGE GAS, O2 MONITOR OK LOG BOOK OK ONE INSTALLER |