Permit: T07CM00914

Parcel: 10319001P

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00914

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/11/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. EXISTING SERVICE NOT GROUNDED. REINSTALL GROUNDING ELECTRODE SYSTEM PER 250 NEC
ENCLOSURES
2. NEUTRAL IS BONDED AT SERVICE DISCONNECT, ISOLATE GROUNDS & NEUTRALS AT BREAKER PANEL
3. CHECK OUT CONDUCTORS IN GUTTER, SOME ARE DETERIORATED -- INSULATION RUBBING INTO CONDUIT.
4. INSTALL PERMANENT ADDRESS LABEL ON SERVICE
ALSO, TAGS OR LABELS AS TO EQUIP. FEEDING - MODULAR, ETC.
5. CHECK OUT GROUNDING INTEGRITY AT REMOTE PANEL BY MODULAR, BREAKERS IN PANEL HAVE WATER DAMAGE, RUST, CHECK OUT & CLEAN ALL TERMINATIONS.