Permit: T07CM00815

Parcel: 136382240


Addresses:

4734 S GOLDENROD PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/06/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/13/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE MAXIMUM NUMBER OF SWITCHES WITH OUT MAIN DISCONNECT IS 6, YOU HAVE 10
2) LABEL ALL BREAKERS
3) NEED MINIMUM 50 AMP BREAKER MINIMUM CIRCUIT AMPS
4) MAX LENGTH ON FLEX CONDUIT 6' (USE RIGID, SUPPORTED), JOINT IS COME APART AT DISCONNECT
5) MARK UNIT GAS DEMAND ON UNIT 1/2" DIAMETER PIPE RISER ?
6) CONDENSATE LINE NOT SUPPORTED OR DRAINING OFF ROOF
7) TWO POLE 30 AMP CIRCUIT GRD. IS CUT OFF
8) U.L. LABEL ON YOUR PANEL, USE ONLY MURRAY AND SIEMENS BRAND BREAKERS
9) NEED TWO GROUND RODS-GAS BOND AND H20 BOND