Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00243
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK KITCHEN - LV CABLING IN CIP TRAINING MUST HAVE OWN SUPPORTS, CABLE OFF GRID |
|
| 04/03/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - DO NOT SUPPORT MC CABLE TO CONDUITS - COMPLETE ALL LOW VOLTAGE CABLING & SUPPORT TO STRUCTURE PER NEC. 725 THRU 800 |
|
| 04/01/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - OK SMALL OFFICES - CIP TRAINING NOT READY |
|
| 01/22/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/04/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/28/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LIDS ENTRY LOBBY SOFFIT ROOM 400, NORTHWEST LOBBY ENTRANCE RM 444, RESTROOM 402, 403 AND JANITOR ROOM 442 |
|
| 12/17/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |