Permit: T07CM00242

Parcel: 13819045B

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM00242

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/11/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ISOLATORS ON REFRIGERATION LINE SETS ENTERING UNITS (RUBBER GROMMITS)
2. NO GALVANIZED AND COPPER CONTACT
3. PROVIDE BUG SCREEN OR RTU O.S.A INLET
4. INSULATE CONDENSATE PIPING
5. PROVIDE SECONDARY DRAINS ON FAN COILS