Permit: T07CM00183

Parcel: 12111022A


Addresses:

4927 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
02/05/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
08/28/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK SERVICE AREA
08/24/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. 8 - 4" PVC'S TEP TRANS TO NEW SES
2. 6 - 4" PVC'S SES TO ATS
3. 6 - 4" PVC'S ATS TO GENERATOR
4. 6 - 4" PVC'S ATS TO MTS
5. 6 - 4" PVC'S MTS TO INTERIOR BLD
6. 6 - 4" PVC'S MTS TO PGC-B
7. 6 - 3" PVC'S SES TO INTERCEPT EXT SERS
8. VARIOUS CONDUITS TO J-BOX

ALL UNDERGROUND CONDUITS AT SERVICE, TRANSFER SW'S
GENERATOR AREAS