Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2007 | ELECTRIC - UFER | Approved | IVRS - Inspection :* INSTALL NEW SERVICE (ELECT) NEW BACK UP GENERATION APPROVED SERVICE & SYSTEM GROUNDING 1. GROUNDING SYSTEM PER E-100B FOR SERVICE & EQUIPMENT AREA - CONSISTING OF 8 GROUND RODS, TIE INTO EXISTING SYSTEM, VARIOUS #25 BTC TO BOLLARDS AND ALL EQUIPMENT AS PER PLAN NOTES 2. 4/0 COPPER UFER TO 3 GROUND RODS AT 6' APART FOR SERVICE GROUND. RECEIVED $108.00 FROM JOBSITE FOREMAN JOE PORTILLO BROKEN ARROW COMM FOR INSPECTION SPECIAL INSPECTION ON GROUNDING |