Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2007 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* WT = 78 PSF (W MEDIUM WT 115PLF) 1" STUCCO FINISH EA. SIDE = 2 X 12 PSF = 20 PSF DL = 78+20 = 98 PSF TOTAL LOAD = P=98PSF (9.33 X 7.08+4.67 X 2.33) = 7540# WIND LOAD = 19.84 PSF (9.33' X 6.58' + 4.67 X 2.33') = 1434# SEISMIC BASE SHEAR V=0.248 W/1.4 = 0.177W SEISMIC LOAD F=0.177 [98 PSF (9.33' X 6.58' + 4.67' X 2.33')] = 1254# 1254# < 1434# *WIND GOVERNS V = 1434# M = 1434# X (8.92'/2 + 0.50') = 7113# |
|
| 06/26/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS TO TOPOUT 8'11" MUST PROVIDE BY ENGINEER TO USE 8X8X16 (NOM. 7 1/2 X 7 1/2 X 15 1/2) INSTEAD 10" CMU MUST PROVIDE RFI STAMPED BY ENGINEER |
|