Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/17/2007 |
FIRE - KITCHEN EXH HOOD FINAL |
|
Approved |
|
| 05/16/2007 |
FIRE - KITCHEN EXH HOOD FINAL |
|
Denied |
While testing the alarm for the Kitchen hood system it was noticed by silencing the alarm at the fire alarm panel the hood electrical system for the hood appliances came back on. The only way to reset appliances is by resetting the Ansul system by a licensed hood extinguisher system tech and not by pushing a silencing button or reset button at the fire alarm panel. |