Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
05/17/2007 FIRE - KITCHEN EXH HOOD FINAL Approved
05/16/2007 FIRE - KITCHEN EXH HOOD FINAL Denied While testing the alarm for the Kitchen hood system it was noticed by silencing the alarm at the fire alarm panel the hood electrical system for the hood appliances came back on. The only way to reset appliances is by resetting the Ansul system by a licensed hood extinguisher system tech and not by pushing a silencing button or reset button at the fire alarm panel.