Permit: T06PL02402

Parcel: 127021990


Addresses:

5349 E BAKER ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/27/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
READ ALL NOTES & COMPLY
1. DRAFT HOOD TO BE CONNECTED PROPERLY
2. ALL VENT CONNECTIONS TO BE MADE UP CORRECTLY AND SECURED WITH SHEETMETAL SCREWS.
3. T&P DRAIN TO BE CUT OFF 1" ABOVE MINIMUM FROM TOP LIP OF DRAIN PAN - NOTIFIED OWNER OF DANGEROUS CONDITION FOR VENT NOT CONNECTED ASKED HER TO SHUT OFF WATER HEATER. TOLD HER HOW TO. FAILURE TO COMPLY SHALL RESULT IN REFEE.

PETITION OF APPEAL #2006-240 ON SITE

4. REMOVE PAPER AT CEILING LEVEL FROM DOUBLE
WALL VENT
08/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO ONE HOME
02/27/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE PETITION OF APPEAL FOR RELIEF DRAIN
2. CORRECT VENT CONNECTOR!
3. USE GALV SHEET METAL SCREWS AT EACH JOINT.
4. YOU HAVE USED TAPE TO COVER A LEAK ON VENT.
5. YOU MAY NOT USE ANY TAPE ON ANY JOINT.
6. EXTEND VENT TO 3' ABOVE COOLER
7. USE A NEW GAS SUPPLY CONNECTOR AND SOAP TEST JOINTS.
8. INSTALL AN OPERATING FULL PORT SHUT OFF VALVE ON WATER SUPPLY.
9. GALV NIPP ON HW HAS AN OBVIOUS LEAK.