Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* READ ALL NOTES & COMPLY 1. DRAFT HOOD TO BE CONNECTED PROPERLY 2. ALL VENT CONNECTIONS TO BE MADE UP CORRECTLY AND SECURED WITH SHEETMETAL SCREWS. 3. T&P DRAIN TO BE CUT OFF 1" ABOVE MINIMUM FROM TOP LIP OF DRAIN PAN - NOTIFIED OWNER OF DANGEROUS CONDITION FOR VENT NOT CONNECTED ASKED HER TO SHUT OFF WATER HEATER. TOLD HER HOW TO. FAILURE TO COMPLY SHALL RESULT IN REFEE. PETITION OF APPEAL #2006-240 ON SITE 4. REMOVE PAPER AT CEILING LEVEL FROM DOUBLE WALL VENT |
|
| 08/22/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NO ONE HOME |
|
| 02/27/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PETITION OF APPEAL FOR RELIEF DRAIN 2. CORRECT VENT CONNECTOR! 3. USE GALV SHEET METAL SCREWS AT EACH JOINT. 4. YOU HAVE USED TAPE TO COVER A LEAK ON VENT. 5. YOU MAY NOT USE ANY TAPE ON ANY JOINT. 6. EXTEND VENT TO 3' ABOVE COOLER 7. USE A NEW GAS SUPPLY CONNECTOR AND SOAP TEST JOINTS. 8. INSTALL AN OPERATING FULL PORT SHUT OFF VALVE ON WATER SUPPLY. 9. GALV NIPP ON HW HAS AN OBVIOUS LEAK. |