Permit: T06PL02169

Parcel: 112030080


Addresses:

2718 E PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/01/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
12/01/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
TEST IS OK
SUPPORT VERTICAL PIPE AT WH AND FURNACE
PROTECT BELOW GROUND PIPING W/PRIMER AND 10 MIL TAPE
OK FOR GAS AFTER CORRECTING
OK TO FINAL AFTER APPROVING FAV
11/29/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAVE NEW FAV INSPECTED AND PROVIDE PROOF OF INSPECTION.
2. COMPLETE VENTING OF FAV AND WH
3. TEST ALL GAS PIPING INCLUDING TEES WITH A 15 PSI
4. GAUGE WITH 1/10 PSI INCREMENTATIONS.
5. SECURE PIPING IN ATTIC

NOTE: THE USE OF CSST IS ACCEPTABLE WHEN SHOWN ON PLAN. T&P APPEARS TO HAVE BEEN INSTALLED UNDER PRIOR CODES AND CAN REMAIN UNTIL WH IS REPLACED.