Permit: T06PL01679

Parcel: 130021470


Addresses:

2910 E 23RD ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/30/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
10/11/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- THE ENTIRE GAS SYSTEM SHALL BE BROUGHT UP TO CURRENT CODE REQUIREMENTS.
- THE INSTALLATION AND RELOCATION OF NEW HEAT PUMP AND INSTANTANEOUS WH REQUIRE SEPARATE PERMITS.
- OBTAIN A MECHANICAL PERMIT AND HAVE FURNACE INSPECTED PRIOR TO GAS PIPING INSPECTION.
- ALSO, PROVIDE PROOF OF STRUCTURAL FRAMING INSPECTION FOR NEW ROOF. NOTE: PLUMBING VENTS NEED TO TERMINATE ABOVE NEW ROOF.
- 3/4" GAS PIPING TO 199,000 BTU WH AND 69,000 BTU FURNACE, STOVE AND DRYER IS UNDERSIZED. PLEASE PROVIDE A CITY APPROVED ISOMETRIC DRAWING OF GAS SYSTEM.
- OLD FURNACE & PIPING SHALL BE REMOVED IF NOT OPERABLE
- VENTING ON WH NOT CORRECTLY INSTALLED
- BELOW GRADE PIPING SHALL BE PRIMERED AND WRAPPED AT FITTINGS & TEST MARKS, 15 PSI GAUGE REQUIRED FOR TEST.