Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/11/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - THE ENTIRE GAS SYSTEM SHALL BE BROUGHT UP TO CURRENT CODE REQUIREMENTS. - THE INSTALLATION AND RELOCATION OF NEW HEAT PUMP AND INSTANTANEOUS WH REQUIRE SEPARATE PERMITS. - OBTAIN A MECHANICAL PERMIT AND HAVE FURNACE INSPECTED PRIOR TO GAS PIPING INSPECTION. - ALSO, PROVIDE PROOF OF STRUCTURAL FRAMING INSPECTION FOR NEW ROOF. NOTE: PLUMBING VENTS NEED TO TERMINATE ABOVE NEW ROOF. - 3/4" GAS PIPING TO 199,000 BTU WH AND 69,000 BTU FURNACE, STOVE AND DRYER IS UNDERSIZED. PLEASE PROVIDE A CITY APPROVED ISOMETRIC DRAWING OF GAS SYSTEM. - OLD FURNACE & PIPING SHALL BE REMOVED IF NOT OPERABLE - VENTING ON WH NOT CORRECTLY INSTALLED - BELOW GRADE PIPING SHALL BE PRIMERED AND WRAPPED AT FITTINGS & TEST MARKS, 15 PSI GAUGE REQUIRED FOR TEST. |