Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2007 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* OK TO BACKFILL TRENCH 15 PSI TEST IS OK |
|
| 02/09/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS ISOMETRIC ON SITE 1. VENT FROM NEW WATER HEATER REQUIRES CORRECT VENT FITTINGS AND MINIMUM 1" CLEARANCE THRU ROOF & COMBUSTIBLES. 2. WATER HEATER REQUIRES SEDIMENT TRAP AND CORRECTLY RATED FLEX FOR 199,900 BTU APPLIANCE. 3. WATER HEATER REQUIRES TEMPERATURE & PRESSURE RELIEF DEVICE WITH DRAIN PIPING. 4. SHALL PROVIDE BONDING OF BUILDING GAS PIPING. PROVIDE WATER HEATER PERMIT ROOFTOP UNIT PERMIT WITH PROOF OF APPROVAL OF INSPECTION FOR GAS CARD. 5. PROVIDE WORKING TEST GAUGE IN 1/10TH POUND INCREMENTS. 6. PROVIDE SEDIMENT TRAP FOR FURNACE. |
|
| 01/19/2007 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE NOTES FROM 10/11/06 INSPECTION 2. YOUR TOTAL BTU DEMAND IS 343,000 AND AT YOUR DISTANCE 1" PIPING IS UNDERSIZED. PROVIDE CITY APPROVED GAS ISOMETRIC WITH PERMITS & INSPECTIONS OF ALL ITEMS LISTED ON 10/11/06 INSPECTION. 3. NOTE ANY FUTURE TEE CONNECTIONS SHALL BE ON CITY APPROVED PLAN -- NOT COMPLETE LIST. |
|
| 10/11/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |