Permit: T06PL01679

Parcel: 130021470


Addresses:

2910 E 23RD ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/21/2007 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
OK TO BACKFILL TRENCH
15 PSI TEST IS OK
02/09/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAS ISOMETRIC ON SITE
1. VENT FROM NEW WATER HEATER REQUIRES CORRECT VENT FITTINGS AND MINIMUM 1" CLEARANCE THRU ROOF & COMBUSTIBLES.
2. WATER HEATER REQUIRES SEDIMENT TRAP AND CORRECTLY RATED FLEX FOR 199,900 BTU APPLIANCE.
3. WATER HEATER REQUIRES TEMPERATURE & PRESSURE RELIEF DEVICE WITH DRAIN PIPING.
4. SHALL PROVIDE BONDING OF BUILDING GAS PIPING.
PROVIDE WATER HEATER PERMIT
ROOFTOP UNIT PERMIT WITH PROOF OF APPROVAL OF INSPECTION FOR GAS CARD.
5. PROVIDE WORKING TEST GAUGE IN 1/10TH POUND INCREMENTS.
6. PROVIDE SEDIMENT TRAP FOR FURNACE.
01/19/2007 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEE NOTES FROM 10/11/06 INSPECTION
2. YOUR TOTAL BTU DEMAND IS 343,000 AND AT YOUR DISTANCE 1" PIPING IS UNDERSIZED. PROVIDE CITY APPROVED GAS ISOMETRIC WITH PERMITS & INSPECTIONS OF ALL ITEMS LISTED ON 10/11/06 INSPECTION.
3. NOTE ANY FUTURE TEE CONNECTIONS SHALL BE ON CITY APPROVED PLAN -- NOT COMPLETE LIST.
10/11/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*