Permit: T06PL01609

Parcel: 133210930

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/08/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
300 NORTH
GAS DEMAND IS 300,000 BTU
TOTAL LENGTH APPROX. 60'
1 1/4" PIPING IS REQUIRED TO FIRST FURNACE.
1" REQUIRED TO SUPPLY SECOND FURNACE AND WH
TEE SHALL BE FULL SIZE
PROVIDE PLAN FOR GAS PIPING AND INSTALLATION OF NEW FURNACE.
INSTALLATION OF NEW FURNACE REQUIRES MECHANICAL PERMIT.
HAVE MECHANICAL INSPECTION PRIOR TO GAS INSPECTION.
PETITION OF APPEAL REQUIRED IF T&P CANNOT TERMINATE OUTSIDE.
SEDIMENT TRAPS REQUIRED.
NO TAPE AT VENT CONNECTOR TO VENT CONNECTION
SUPPORT PIPING AT WH
SEAL WALL PENETRATION.