Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - YOUR PERMIT IS FOR RELOCATING GAS METER. - RELOCATING AND REPLACING A GAS WATER HEATER REQUIRES A PERMIT. YOU CAN HAVE THIS ADDED TO THIS PERMIT. - 3/4 PIPING SUPPLING 117,000 BTU WH AND 80,000 BTU FURNACE AT 60' IS UNDERSIZED. - PROVIDE 1" PIPING TO BRANCH CONNECTION FOR WH. - HAVE MECHANICAL INSPECTION APPROVED BEFORE RECALLING |