Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - WATER HEATER PLATFORM IS COLLAPSING. - WH IS LEANING. - T&P TERMINATION IS IN GARAGE. - T&P CONNECTED W/FLEX. FLEX HAS KINK. - CORRECT PLATFORM - PROVIDE DRAIN PAN, MAY DRAIN INTO GARAGE. - TERMINATE T&P OUTSIDE WITH APPROVED MATERIALS, - FLEX IS NOT ALLOWED - REMOVE TAPE FROM SINGLE WALL TO DOUBLE WALL VENT TRANSITION - SECURE VENT W/SCREWS - SEDIMENT TRAP REQUIRED. |
|
| 06/08/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* NOBODY HOME |