Permit: T06PL00705

Parcel: 113032260


Addresses:

919 E MESQUITE DR

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/13/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- WATER HEATER PLATFORM IS COLLAPSING.
- WH IS LEANING.
- T&P TERMINATION IS IN GARAGE.
- T&P CONNECTED W/FLEX. FLEX HAS KINK.
- CORRECT PLATFORM
- PROVIDE DRAIN PAN, MAY DRAIN INTO GARAGE.
- TERMINATE T&P OUTSIDE WITH APPROVED MATERIALS,
- FLEX IS NOT ALLOWED
- REMOVE TAPE FROM SINGLE WALL TO DOUBLE WALL VENT TRANSITION
- SECURE VENT W/SCREWS
- SEDIMENT TRAP REQUIRED.
06/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NOBODY HOME