Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/16/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03050 -- 20 PSI TEST FROM METER ABOVE GROUND TO EXISTING SERVICE ENTRANCE TO ROOFTOP UNIT & WATER HEATER OK
1. PROVIDE CORRECT SUPPORT ON ALL GAS PIPING.
2. PROVIDE DRAIN PIPE FOR WATER HEATER TEMPERATURE & PRESSURE RELIEF
3. MAKE UP VENT FROM WATER HEATER & PROVIDE 3-GALV SCREWS AT EACH JOINT.
4. PROVIDE PRIMER & TEN MIL. TAPE ON PIPING AT RISER AT METER.
GAS CARD AT METER 889-1888