Case: T06FR02875

Parcel: 137105050


Addresses:

5550 S 12TH AV #116


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR02875

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
12/13/2006 VIOL - MEANS OF EGRESS Violation 1003.6 Means of egress continuity. The path of egress travel
along a means of egress shall not be interrupted by any building
element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required
width of a means of egress except projections permitted by this
chapter. Remove stock blocking access to exit door and keep bathroom door closed so as not to block exit door.
12/13/2006 VIOL - MEANS OF EGRESS Violation 1011.2 Illumination. Exit signs shall be internally or externally
illuminated. Illuminate exit signs in rear exit and at front exit.