Full Fire Inspection

Outstanding Inspections

Case Number: T06FR02875
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/13/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
12/13/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. Remove stock blocking access to exit door and keep bathroom door closed so as not to block exit door.
12/13/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Illuminate exit signs in rear exit and at front exit.