Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T06FR02837

Parcel: 121123870


Addresses:

5224 E PIMA ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/01/2007 VIOL - FIRE PROTECTION SYSTEMS Approved All approved.
12/06/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not tagged / inspected:
TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
***1. Extinguishers shall be inspected and tagged in accordance with this code.
12/06/2006 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishing system service:
904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

904.11.6.5 Fusible link and sprinkler head replacement.
Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices
shall be serviced or replaced in accordance with the manufacturer's instructions.
Exception: Frangible bulbs are not required to be replaced annually. system in accordance with Section 903.3.1.1 or 903.3.1.2.
***Service and tag hood system in an approved manner.
***Service [replace] heads on kitchen ceiling and have entire system inspected / tested, approved and tagged.