Case: T06FR02837
Case Details
Entered Date:
12/06/2006
Applicant:
MEABON MARK T & DEBRA A JT/RS
Description:
Full inspection done 12/04/06. Los Carmelos Restaurant. "A-2" occupancy. Marcos Barragan- owner. 631-0014 881-8691 [bus.]
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02837
Case Description: INSPECTION
Total Completed Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Extinguishing system service: 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. 904.11.6.5 Fusible link and sprinkler head replacement. Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer's instructions. Exception: Frangible bulbs are not required to be replaced annually. system in accordance with Section 903.3.1.1 or 903.3.1.2. ***Service and tag hood system in an approved manner. ***Service [replace] heads on kitchen ceiling and have entire system inspected / tested, approved and tagged. |
| 12/06/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Food warmer-burned cord: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ***Remove appliance with burned cord. |
| 12/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | Extinguishers not tagged / inspected: TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ***1. Extinguishers shall be inspected and tagged in accordance with this code. |
| 12/06/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Multiplug adapters: TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Remove noncomplying devices. |
| 12/06/2006 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Extension cords: TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. *** Replace all with approved power strip. |
| 12/06/2006 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Blocked exit: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. ***Clear exit area, and maintain it this way. Note: Please keep this doorway clear, and place a "Employees only" sign on it, and remove "Exit" Sign as it is not a required exit. |
| 12/06/2006 | VIOL - MEANS OF EGRESS | BCOBB | Approved | Double keyed lock on three east rear doors: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. *** Remove Keyed dead bolt and replace with thumb turn type bolts. |
| 12/06/2006 | INSP - FULL | BCOBB | Approved | Please correct the following Tucson Fire Code violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. 2. A record of the sprinkler system inspections shall be made available upon re-inspection. |
| 12/27/2006 | INSP - REINSPECTION | BCOBB | Approved | Still non-compliant; will do this week per owner. |